  • In the function determineNextEvent () the last target time will be the Period length added to calculate the next execution time. If the connection was interrupted for a long time, however, they accumulate many versions of the then with a shorter period length (tv_earliest_next_trigger_time) are processed. If the cycle times anyway are already tightly laid out, this can lead to an overload. Must be changed. The next execution time must be the current time plus Be cycle time.

Error Codes in Process Image

ModbusTCP

Modbus_Master_Status
16 0x10 Initialization is failed
17 0x11 This device is not readable(false IP, Cabel?)
Modbus_Action_Status
1 ILLEGAL FUNCTION The applied function code is not allowed.
Check whether the right function code is used.
2 ILLEGAL DATA ADDRESS The applied address is not valid. The register is either read-only or not existed.
Please check the address.
3 ILLEGAL DATA VALUE At least one part of the applied data is invalid. It is possible that the count of register is exceed.
Please check the value.
13 INVALID DATA The Slave answered with an unknown package to me. This can occur, for example, after the connection has been interrupted.
Please check your wiring.
104 CONNECTION RESET BY
PEER
This is a TCP problem. It can occur if the addressed host has no instance of the modbus slave running.
110 CONNECTION TIMED OUT The slave didn't respond in time or not at all.
Please check your configuration and cabling.

ModbusRTU

Modbus_Master_Status
16 0x10 Initialization is failed
17 0x11 Serial connection can't be opened (wrong device name, invalid configuration)
Modbus_Action_Status
1 ILLEGAL FUNCTION The applied function code is not allowed.
Check whether the right function code is used.
2 ILLEGAL DATA ADDRESS The applied address is not valid. The register is either read-only or not existed.
Please check the address.
3 ILLEGAL DATA VALUE At least one part of the applied data is invalid. It is possible that the count of register is exceed.
Please check the value.
11 FAILED TO RESPOND Resource temporarily unavailable. Usually means that the device is not present on the network.
12 INVALID CRC A disturbed packet was received from the slave. This can occur, for example, after the connection has been interrupted.
Please check your wiring.
13 INVALID DATA An incomplete packet was received from the slave. This can occur, for example, after the connection has been interrupted.
Please check your wiring.
110 CONNECTION TIMED OUT The slave didn't respond in time or not at all.
Please check your configuration and cabling.

All internal error messages that do not occur and do not need to be documented

ID
1 Illegal function
2 Illegal data address
3 Illegal data value
4 Slave device or server failure
5 Acknowledge
6 Slave device or server is busy
7 Negative acknowledge
8 Memory parity error
10 Gateway path unavailable
11 Target device failed to respond
12 Invalid CRC
13 Invalid data
14 Invalid exception code
15 Too many data

Example configuration for the config.rsc

Further information in document about configuration and I/O

{

    "config": {
        "modbusActions": [
            {
                "SlaveAddress" : 1,
                # Address of the Modbus slave which is addressed by the
                # command

                "FunctionCode" : 2,
                # Modbus function code see below

                "RegisterAddress" : 1,
                # Modbus register address (start address) of the slave

                "QuantityOfRegisters" : 8,
                # Number of Modbus registers that are written / read

                "ActionInterval" : 100000,
                # Time interval in which the command is sent from the
                # master in µsec. For the user, information in 1 ms
                # steps is sufficient

                "ProcessImageStartByte" : 2,
                # The offset in the Pi process image for the Modbus data

                "Action ID" : 1
                # Ascending ID for the command for information in the
                # event of an error
            },
            {
                "SlaveAddress" : 1,
                "FunctionCode" : 3,
                "RegisterAddress" : 1200,
                "QuantityOfRegisters" : 8,
                "ActionInterval" : 200000,
                "ProcessImageStartByte" : 18,
                "Action ID" : 2
            },
            {
                "SlaveAddress" : 2,
                "FunctionCode" : 16,
                "RegisterAddress" : 1024,
                "QuantityOfRegisters" : 8,
                "ActionInterval" : 500000,
                "ProcessImageStartByte" : 2,
                "Action ID" : 3
            }
        ]
    }
}

Modbus Function Codes:

Important function codes are marked with '*'.The other function codes may not need to be supported.

Code ID
* eREAD_COILS 0x01
* eREAD_DISCRETE_INPUTS 0x02
* eREAD_HOLDING_REGISTERS 0x03
* eREAD_INPUT_REGISTERS 0x04
* eWRITE_SINGLE_COIL 0x05
* eWRITE_SINGLE_REGISTER 0x06
eREAD_EXCEPTION_STATUS 0x07
* eWRITE_MULTIPLE_COILS 0x0F
* eWRITE_MULTIPLE_REGISTERS 0x10
eREPORT_SLAVE_ID 0x11
eWRITE_MASK_REGISTER 0x16
eWRITE_AND_READ_REGISTERS 0x17

Coils and Discrete Inputs are one bit in size. In the process image, however, one byte should be reserved for each bit.Holding registers and input registers have a size of 2 bytes.

For each Modbus command, an additional byte must be reserved in the Pi process image for error messages.

For the virtual device, a byte must also be reserved in the Pi process image for error messages.

For each Modbus command and the virtual device, a bit must be reserved to reset the error byte in the Pi process image