eldar6776 / DE-020717

Hotel Room Thermostat With Capacitive Touch 4,3" TFT LCD And Audio Codec (STM32F746ZE)

Geek Repo:Geek Repo

Github PK Tool:Github PK Tool

DE-020717

Hotel Room Thermostat With Capacitive Touch 4,3" TFT LCD And Audio Codec

/**


  • Project Name : DE-020717
  • Date : 02.07.2017.
  • Hardware IDE : Altium Designer 16.0.5
  • Firmware IDE : KEIL uVision 5.25.0.0
  • Target Device : STM32F746ZET (LQFP-144, 512 Kbytes Flash, 216 MHz)

  • Feature : Hardware

  • 1 OneWire Serial Port For Connection With Room Control Bus Or Digital Sensors
  • 1 RS485 Serial Port For Connection With Hotel Control Bus
  • 6 Digital Otputs 0,5A 50V For Fancoil Control
  • 2 High Speed Digital Inputs Sensing Mains Phase Zero Crossing And Fan RPM
  • 3 Analog Inputs For Temperature And Light Sensing
  • Audio Codec With Wave Player And 1W Speacker Amplifier Is Used For Audio Signal
  • 2,4GHz Radio Transciever 1Mbps For Wireless Connection To Control Network
  • Battery Connector For RTC Backup
  • 5Vdc Or 12Vdc Power Supply
  • "DE-060418" Or "DE-130418" Is Used As Fancoil Interface
  • "DE-200216" Or "DE-290817" Is Used As Room Controller
  • "Red Dragon 429 Demo Board" Is Used As Hotel Controller

  •  	: Firmware
    

  • Room Temperature Set, Ambient Temperature Monitoring, Fancoil Fan Speed
  • In 3 Manual Presets (Lo, Mid, Hi). Automatic Fancoil Fan Speed With PID
  • Control Loop When Fancoil Fan Motor Is Equipped With RPM Sensor And
  • Triac Is Used For Phase Control Of Fan Motor AC Power Supply. When 3 Speed
  • Fancoil Fan Motor Is Used, Proportional Controller Is Activ In Automatic Mode.
  • Set Thermostat For Cooling Or Heating. Software One Cycle Function Activation
  • Used For Room Preheating Or Precooling To Comfortable Temperature.
  • 7 Days Wheter Forecast Info Screen. Alarm Clock With One Preset.
  • Button For "Do Not Disturb" Function Activation / Deactivation. Message Is
  • Displayed On Outdoor Room Controller Display And Doorbell Is Disabled.
  • Button For "Call Handmaid" Activation / Deactivation. Signal Is Activated
  • On Outdoor Room Controller Display And Call Is Send To Reception PC Software
  • Button For "SOS Reset" When SOS Alarm Is Activated By Pulling SOS Switch In
  • Bathroom.


*/

About

Hotel Room Thermostat With Capacitive Touch 4,3" TFT LCD And Audio Codec (STM32F746ZE)


Languages

Language:C 94.6%Language:HTML 2.0%Language:C++ 2.0%Language:Assembly 1.1%Language:Makefile 0.4%