eLvErDe / check-power-walker-ups

Parse Power Walker UPS (www.powerwalker.com) info and return current state as a Nagios check

Geek Repo:Geek Repo

Github PK Tool:Github PK Tool

Usage

Usage: check_power_walker_ups.py [-h] -H 10.1.2.3 [-P 80] [-iv @225:235 @220:240] [-ov @225:235 @220:240] [-if 48:52 46:54] [-of 48:52 46:54] [-ll :20 :50] [-tc 5:30 :40] [-bc 50: 25:] [-br 60: 30:]

Parse Power Walker UPS (www.powerwalker.com) info and return current state as a Nagios check

Optional arguments:

  • -h, --help
    Show this help message and exit
  • -H 10.1.2.3, --host 10.1.2.3
    IP address or hostname of the UPS
  • -P 80, --port 80
    Port of the UPS HTTP interface
  • -iv @225:235 @220:240, --input-voltage @225:235 @220:240
    Warning/critical thresholds using Nagios-style value for input voltage
  • -ov @225:235 @220:240, --output-voltage @225:235 @220:240
    Warning/critical thresholds using Nagios-style value for output voltage
  • -if 48:52 46:54, --input-frequency 48:52 46:54
    Warning/critical thresholds using Nagios-style value for input frequency
  • -of 48:52 46:54, --output-frequency 48:52 46:54
    Warning/critical thresholds using Nagios-style value for output frequency
  • -ll :20 :50, --load-level :20 :50
    Warning/critical thresholds using Nagios-style value for load level (0-100)
  • -tc 5:30 :40, --temp-celsius 5:30 :40
    Warning/critical thresholds using Nagios-style value for temperature in celsius degrees
  • -bc 50: 25:, --battery-capacity 50: 25:
    Warning/critical thresholds using Nagios-style value for battery capacity (0-100)
  • -br 60: 30:, --battery-remaining 60: 30:
    Warning/critical thresholds using Nagios-style value for battery remaining time in minutes

Example

python3 check_power_walker_ups.py  --host 10.1.2.3 --input-voltage @225:239 @220:242 --input-frequency 48:52 46:54 --load-level :20 :50 --temp-celsius '5:30' ':40' --battery-capacity 50: 25: --battery-remaining 60: 30:
OK: UPS is doing fine: in: 235.2V, 50.0Hz, load: 14%, remaining: 287min, temp: 20.0°C | input_voltage=235.2V, output_voltage=229.9V, input_frequency=50.0Hz, output_frequency=50.0Hz, output_current=1.2A, battery_capacity=100%, battery_remaining_time=287min, battery_voltage=82.0V, load_level=14%, temp_celsius=20.0°C
python3 check_power_walker.py  --host 10.1.2.3 --input-voltage @225:239 @220:242 --input-frequency 48:52 46:54 --load-level :20 :50 --temp-celsius '5:15' ':19' --battery-capacity 50: 25: --battery-remaining 500: 100:
CRITICAL: Temp C: 20.0>=19.0, Batt Remain: 287<=500.0 | input_voltage=235.6V, output_voltage=229.6V, input_frequency=50.0Hz, output_frequency=50.0Hz, output_current=1.1A, battery_capacity=100%, battery_remaining_time=287min, battery_voltage=82.0V, load_level=13%, temp_celsius=20.0°C

About

Parse Power Walker UPS (www.powerwalker.com) info and return current state as a Nagios check

License:The Unlicense


Languages