My modification of Python script for reading data from Eastron SDM630 over ModBus
All registers
MODBUS offset | Description | Units |
---|---|---|
2 | Phase 2 line to neutral volts | Volts |
4 | Phase 3 line to neutral volts | Volts |
6 | Phase 1 current | Amps |
8 | Phase 2 current | Amps |
10 | Phase 3 current | Amps |
12 | Phase 1 power | Watts |
14 | Phase 2 power | Watts |
16 | Phase 3 power | Watts |
18 | Phase 1 volt amps | VoltAmps |
20 | Phase 2 volt amps | VoltAmps |
22 | Phase 3 volt amps | VoltAmps |
24 | Phase 1 volt amps reactive | VAr |
26 | Phase 2 volt amps reactive | VAr |
28 | Phase 3 volt amps reactive | VAr |
30 | Phase 1 power factor (1) | None |
32 | Phase 2 power factor (1) | None |
34 | Phase 3 power factor (1) | None |
36 | Phase 1 phase angle | Degrees |
38 | Phase 2 phase angle | Degrees |
40 | Phase 3 phase angle | Degrees |
42 | Average line to neutral volts | Volts |
46 | Average line current | Amps |
48 | Sum of line currents | Amps |
52 | Total system power | Watts |
56 | Total system volt amps | VA |
60 | Total system var | VAr |
62 | Total system power factor (1) | None |
66 | Total system phase angle | Degre es |
70 | Frequency of supply voltages | Hz |
72 | Import wh since last reset (2) | kWh / MWh |
74 | Export wh since last reset (2) | kWH / MWh |
76 | Import varh since last reset (2) | kVArh / MVArh |
78 | Export varh since last reset (2) | kVArh / MVArh |
80 | Vah since last reset (2) | kVAh / MVAh |
82 | Ah since last reset(3) | Ah / kAh |
84 | Total system power demand (4) | Watts |
86 | Maximum total system power | Watts |
100 | Total system va demand | VA |
102 | Maximum total system va demand | VA |
104 | Neutral current demand | Amps |
106 | Maximum neutral current demand | Amps |
200 | Line 1 to line 2 volts | Volts |
202 | Line 2 to line 3 volts | Volts |
204 | Line 3 to line 1 volts | Volts |
206 | Average line to line volts | Volts |
224 | Neutral current | Amps |
234 | Phase 1 l/n volts thd | % |
236 | Phase 2 l/n volts thd | % |
238 | Phase 3 l/n volts thd | % |
240 | Phase 1 current thd | % |
242 | Phase 2 current thd | % |
244 | Phase 3 current thd | % |
248 | Average line to neutral volts thd | % |
250 | Average line current thd | % |
254 | -total system power factor (5) | Degrees |
258 | Phase 1 current demand | Amps |
260 | Phase 2 current demand | Amps |
262 | Phase 3 current demand | Amps |
264 | Maximum phase 1 current demand | Amps |
266 | Maximum phase 2 current demand | Amps |
268 | Maximum phase 3 current demand | Amps |
334 | Line 1 to line 2 volts thd | |
336 | Line 2 to line 3 volts thd | |
338 | Line 3 to line 1 volts thd | |
340 | Average line to line volts thd |