"Illegal function" response when read/write coils

yanxin9210 opened this issue · comments

It returns "Illegal function" when I read or write coils.
Version: 3.0.5
Code:

    public static void main(String[] args) {
        IpParameters ipParameters = new IpParameters();
        ipParameters.setHost("192.168.31.200");
        ipParameters.setPort(502);

        ModbusFactory modbusFactory = new ModbusFactory();
        ModbusMaster master = modbusFactory.createTcpMaster(ipParameters, false);
        int slaveId = 1;
        try {
            master.init();
            readCoilTest(master, slaveId, 0, 1);
        } catch (ModbusInitException e) {
            e.printStackTrace();
        }
    }

    public static void readCoilTest(ModbusMaster master, int slaveId, int start, int len) {
        try {
            ReadCoilsRequest request = new ReadCoilsRequest(slaveId, start, len);
            ReadCoilsResponse response = (ReadCoilsResponse) master.send(request);

            if (response.isException()) {
                System.out.println("Exception response: message=" + response.getExceptionMessage());
            } else {
                System.out.println(Arrays.toString(response.getBooleanData()));
            }
        } catch (ModbusTransportException e) {
            e.printStackTrace();
        }
    }

Logs:

10:58:15.121 [main] DEBUG com.serotonin.modbus4j.ip.tcp.TcpMaster - Encap Request: 00 01 00 00 00 06 01 01 00 00 00 01 
10:58:15.137 [main] DEBUG com.serotonin.modbus4j.ip.tcp.TcpMaster - Sending on port: 502
10:58:15.219 [main] DEBUG com.serotonin.modbus4j.ip.tcp.TcpMaster - Response: 00 01 00 00 00 03 01 81 01 
Exception response: message=Illegal function

see your log,00 01 00 00 00 03 01 81 01 , 81 is error code,normally,it will return function code,so the 81 is Illegal function code ,please use the modscan32 check you slave device.
which you company is?

commented

your slave modbus server may not support some functions.

commented

The reason is that you have no create Mbslave in modbus slave